Vessel with One Inlet and One Outlet (smLevelCyl)

Brief Description and Purpose

A function block that simulates the operation of level sensors for a vessel with one inlet and one outlet, used in the simulation model as dosing vessels D1 and D2 (Fig. 1).

img

Fig. 1. Image of the simulated installation for testing PACFramework blocks.

The block receives inlet and outlet flow rates (in m³/s or L/s) as inputs, and outputs the level value L in meters or centimeters depending on the input units. It also simulates the LSH (high-level sensor) and LSL (low-level sensor) signals.

The parameters V0, Vmax, and S are set externally or by default. The parameter d_t defines the call period for correct dynamic calculation and can be used to adjust the simulation speed.

Implementation in IEC-61131

ST

FUNCTION_BLOCK "smLevelCyl1"

   VAR_INPUT 
      INIT : Bool;   // initialization command (sets initial conditions)
      Fin : Real;    // inlet flow rate specified in m3/s or L/s
      Fout : Real;   // outlet flow rate specified in m3/s or L/s
   END_VAR

   VAR_OUTPUT 
      L : Real;      // level in meters or centimeters
      LSH : Bool;    // high-level sensor
      LSL : Bool;    // low-level sensor
   END_VAR

   VAR 
      d_t : Real := 0.1;   // call period in seconds
      V0 : Real;           // initial volume value during model initialization
      V : Real;            // liquid volume in the vessel
      Vmax : Real := 50.0; // vessel volume
      S : Real := 20.0;    // specified in m2 for m3/s or cm2 for L/s
   END_VAR
   
BEGIN
    IF INIT THEN
        V := V0; (* set to minimum volume on initialization *)
    ELSE
        V := V + d_t * (Fin - Fout); (* volume increment *)
        IF V < 0.0 THEN V := 0.0; END_IF; (* lower limit *)
        IF V > Vmax THEN V := Vmax; END_IF; (* upper limit *)
        L := V / S; 
        LSH := (V / Vmax) > 0.999; (* high-level sensor *)
        LSL := (V / Vmax) > 0.001; (* low-level sensor *)
    END_IF;
END_FUNCTION_BLOCK